Credit Cards Accepted
Live Support: 800-521-4045

B100 Bodine Ballast

Brand: Philips Bodine


See PRODUCT DESCRIPTION below The B100 Bodine Ballast may have either been discontinued or may no longer be available.
When you order the B100 Bodine Ballast, we may substitute with equivalent or better product.

Scroll down to view substitute product(s) below.

$72.15

PRODUCT VARIATIONS

$72.15

/ea as Configured

Weight: 3 lbs
SKU: 01:39:B100
Product Name: B100 Bodine Ballast B100 Bodine Ballast
UPC: 00663015103908


DESCRIPTION


APPLICATION 
The B100 emergency ballast works in conjunction with an AC ballast to convert new or existing fluorescent fixtures into emergency lighting. The emergency ballast consists of a high-temperature nickelcadmium battery, charger and electronic circuitry. The B100 can be used with most 32 - 40 W (2’ - 4’) T8, T10, or T12 fluorescent lamps without an integral starter, including U-shaped. It is also compatible with most one-, two-, three- and four-lamp electronic, standard, energy-saving and dimming AC ballasts. If used in an emergency-only fixture, no AC ballast is necessary. The B100 is suitable for indoor and damp locations and for sealed & gasketed fixtures, including fixtures rated for wet locations. It is not suitable for air handling heated air outlets or wet or hazardous locations. For information about specific lamp and ballast compatibility, please call the factory.
 
OPERATION 
When AC power fails, the B100 immediately switches to the emergency mode, operating one lamp at a reduced lumen output for a minimum of 90 minutes. When AC power is restored, the emergency ballast automatically returns to the charging mode and, using a patented circuit, delays AC ballast operation for approximately three seconds to prevent false tripping of the AC ballast end-of-lamp-life shutdown circuits.

INSTALLATION 
The B100 does not affect normal fixture operation and may be used with either a switched or unswitched fixture. If a switched fixture is used, an unswitched hot lead must be connected to the emergency ballast. The emergency ballast must be fed from the same branch circuit as the AC ballast. The B100 may be installed inside, on top of or remote from the fixture. The emergency ballast may be remotely installed up to half the distance the AC ballast manufacturer recommends remoting the AC ballast from the lamp or up to 50 feet, whichever is less. Installation is not recommended with fixtures where the ambient temperature may fall below 0°C.

This item can replace: I-32, B100, DEB-1W, UFO-3AW, FP450, C450, FPSI-32, FH7, L450, MF40-100, EFP 32GS, EFB40, FP-500LP, EP 500, FTU2485, XEB-55, AM32-L, PS300, PL4SC8, F40, S35F, UP40, FBP140X