B94C Bodine Ballast

Brand: Philips Bodine


See PRODUCT DESCRIPTION below The B94C Bodine Ballast may have either been discontinued or may no longer be available.
When you order the B94C Bodine Ballast, we may substitute with equivalent or better product.

Scroll down to view substitute product(s) below.

$219.13

Need quantities of 15 or more? Call us at (800) 521-4045 for possible reduced pricing.

Weight: 3 lbs
SKU: 01:39:B94c
Product Name: B94C Bodine Ballast Bodine | B94C | Bodine Ballast


Replacement or Equivalent Products

DESCRIPTION


B94C
B 94 C
B-94-C

** DISCONTINUED, USE B94CGU BELOW **
 
Fluorescent Emergency Ballast One or two-lamp emergency illumination for 4-pin fluorescent lamps (without integral starter) 

APPLICATION
The B94C fluorescent emergency ballast works in conjunction with the AC ballast to convert new or existing fluorescent fixtures into emergency lighting. The emergency ballast consists of a high-temperature nickel cadmium battery, charger and electronic circuitry in one compact red case.
The B94C can be used with one or two 6 W to 28 W tubular fluorescent lamps without integral starters, or one 13 W to 42 W or two 13 W to 39 W (4-pin) twin, quad, and triple twin-tube compacts. It is also compatible with most 1, 2, 3, and 4-lamp electronic, standard, energy saving, and dimming AC ballasts. If used in an emergency-only fixture, no AC ballast is necessary. The B94C is not suitable for use in air handling heated air outlet fixtures, and wet, damp, or hazardous location fixtures. For information about specific lamp and ballast compatibility, please call the factory.
 
OPERATION
When AC power fails, the B94C immediately switches to the emergency mode, keeping one or two lamps illuminated at a reduced lumen output for a minimum of 90 minutes. When AC power is restored, the B94C automatically returns to the charging mode.
 
INSTALLATION
The B94C does not affect normal fixture operation and may be used with either a switched or unswitched fixture. If a switched fixture is used, an unswitched hot lead must be connected to the emergency ballast. The emergency ballast must be fed from the same branch circuit as the AC ballast. The B94C may be installed on top of or remote from the fixture. The emergency ballast may be remote-installed up to half the distance the AC ballast manufacturer recommends remoting the AC ballast from the lamp, or up to 50 feet, whichever is less. For simple visual inspection of the charging indicator light and easy operational testing, the test/monitor plate can be installed near the fixture wall switch. Or, it can be installed in the ceiling near the fixture to ensure an unobtrusive installation. Installation is not recommended with fixtures where the ambient temperature may fall below 0°C for extended periods. Upon request, a single pole test switch/monitor plate is provided for remote installation of the test switch and charging indicator.
 
UL and CODE COMPLIANCE
The B94C has been tested by Underwriters Laboratories in accordance with the standards set forth in UL924 – "Emergency Lighting and Power Equipment,” and is UL Listed for factory installation or field retrofit. Emergency illumination time exceeds the National Electrical Code (NEC), Life Safety Code (NFPA–LSC) and UL 90-minute requirements.
 
BATTERY
Since high temperatures exist in fluorescent fixtures, the B94C uses a specially constructed, high-temperature nickel cadmium battery. This battery requires no maintenance, and has a life expectancy of 7 to 10 years.
 
EMERGENCY ILLUMINATION
Depending on the number (1 or 2), wattage, and type of lamps selected, the B94C produces 300 to 750 lumens initial emergency light output (See Table 1). If two-lamp operation is selected, light output is evenly divided between the lamps for better distribution of emergency illumination. Emergency lumen output will be less with one-lamp operation. 
 
 
TABLE 1
LAMP TYPE (4-PIN) LUMENS
1 LAMP 2 LAMPS
PL-T 42 W/4P, DULUX T/E 42 W 750  
PL-T 32 W/4P, DULUX T/E 32 W 575 750
PL-T 26 W/4P, DULUX T/E 26 W, F26TBX/4P 450 725
PL-T 18 W/4P, DULUX T/E 18 W, F18TBX/4P 300 525
PL-C 26 W/4P, DULUX D/E 26 W, F26DBX/4P 600 700
PL-C 18 W/4P, DULUX D/E 18 W, F18DBX/4P 475 575
PL-C 13 W/4P, DULUX D/E 13 W, F13DBX/4P 350 425
PL-L 40 W, DULUX L 40 W, F40/30BX/4P 650  
PL-L 36 W, DULUX L 39 W, F39/36BX/4P 575 750
PL-L 24 W, DULUX L 27 W, F27/24BX/4P 475 550
PL-L 18 W, DULUX L 18 W, F18 BX 300 400
F382D/4P 525 650
FO25, FBO24 T8 525 700
FQL 28 600 700
FO17, FBO16 T8 425 500
* Partial list of lamps operated.

 

SPECIFICATION
Emergency lighting shall be provided by using a standard fluorescent fixture equipped with a Bodine B94C emergency ballast. This emergency ballast shall consist of a high-temperature, maintenance-free nickel cadmium battery, charger and electronic circuitry contained in one 9 3/8" x 2 3/8" x 1 1/2" red metal case with 2' lengths of flexible conduit at each end. A test/monitor plate with a solid-state charging indicator light to monitor the charger and battery, a single-pole test switch, and installation hardware shall be provided. The emergency ballast shall be capable of operating [one or two] _________ fluorescent lamp(s) at _________lumens (See Table 1) initial light output in the emergency mode for a minimum of 90 minutes. The B94C shall produce 300 to 750 lumens initial emergency light output, have 3.5 Watts of input power, a 14.4 Watt-hour battery capacity, and comply with emergency standards set forth by the current NEC. The emergency ballast shall be UL Listed for installation on top of or remote from the fixture, warranted for a full two years from date of purchase, and made in the U.S.A.
 
WARRANTY
Model B94C is warranted for two (2) full years from date of purchase. This warranty covers only properly installed Bodine emergency ballasts used under normal conditions. For the warranty period Bodine will, at its option, repair or replace without charge a defective emergency ballast, provided it is returned to the factory transportation prepaid, and our inspection determines it to be defective under terms of the warranty. Repair or replacement, as stated above, shall constitute the purchaser’s exclusive warranty, which does not extend to transportation, installation, labor or any other charges; nor does it apply to any equipment of another manufacturer used in conjunction with the emergency ballast.
 
PRODUCT SUMMARY

UL LISTED Factory or Field Installation
Initial Light Output 300 - 750 Lumens (See Table 2)
Illumination Time 90 Minutes
Test Switch Single Pole
Charging Indicator Light LED
Recharge Time 24 Hours
Ballast Temp. Rating 0°C to + 55°C
Dual Input Voltage 120/277 VAC, 60 Hz
Charging Current 280 mA
Battery High-Temperature, Maintenance-Free, Nickel-Cadmium Battery
7 to 10 Year Life Expectancy
Electrical Rating 3.5 Watts
Warranty 2 Years (NOT pro-rata)
Weight 3.0 lbs.
Dimensions 9.4" x 2.4" x 1.5" (238 mm x 60 mm x 38 mm)
Mounting center 8.9" (226 mm)
2' (610 mm) flexible conduit


Emergency ballasts can be modified to accommodate special voltages, frequencies, and longer run times. For applications where non-conduit model is needed, order model B94. For damp locations order model BDL940 or BDL94C. 